Troubleshooting – Refrigerant Compressor
Webasto Product N.A., Inc. 34 www.techwebasto.com
6.4.3 Checking for Other Electrical Problems
in Single Phase Motors
This section provides procedures for checking the
components such as the thermal protector, relay and
capacitor in a single phase compressor.
The BlueCool Truck System uses a specifically designed
refrigerant compressor for this assembly. The compressor
electrical motor is the type, PSC with external surface
mounted thermal and current overload protection.
This system also uses a run capacitor and a start capacitor
with an internal relay.
The electrical system of this type of compressor motor is
shown in Fig. 34.
Figure 34. PSC Compressor Motor with External Thermal/
Current Protector, Run Capacitor and Start
Capacitor
C
S
R
Overheat/Overload
Protector
Run
Capacitor
Start
Capacitor
(with relay)
Line 1 + 60 VAC (Black)
Line 2 – 60 VAC (White)
Ground (Green)
Compressor Unit
Ground
Main Motor Winding
Start Winding
Compressor Housing
Black
Black
White White
Red/Black Stripe
Black
DC/AC Power Inverter
Green
Table 11. Troubleshooting PSC Compressor Circuits
Step 1: Before Continuing with
Troubleshooting...
All electric power should be disconnected and you should
have already made sure that the compressor does not have
a ground fault (see “Checking for a Ground Fault” on
page 32).
You should have also checked the windings for continuity and proper
resistance (see “Checking for Continuity and Proper Resistance” on
page 33) making sure the system is getting proper voltage and that all
controls, thermostats, etc. are working properly.
Step 2: Check Wiring Confirm that there is continuity between C and the thermal protector
common lead wire.
Step 3: Check External Thermal
Protector
Check for continuity across the thermal protector. If there is no continuity,
then the thermal protector may be tripped. Wait at least 5 minutes, then
check continuity again. If there is still no continuity, replace the thermal
protector.